Megger PAT450 PAT Tester
- 110V and flash testing complements regular 230V appliance testing
- High duty cycle and instant restart increase testing efficiency
- Huge internal memory capacity for 10,000 downloadable records
The Megger PAT450 is a top of the range downloadable PAT tester, complete with 110V operation, vast onboard memory and 1.5kV/3kV flash testing capabilities. The PAT450 is perfectly designed for quick and efficient PAT testing on construction sites, production lines and in hire & repair workshops.
The Megger PAT450 portable appliance tester has full database functionality with an onboard memory that will hold up to 10,000 records; these can then be downloaded via USB to a PC for further trending and analysis. While the QWERTY keyboard and direct access buttons create a free flowing and intuitive PAT testing process, particularly suited to experienced users.
This comprehensive PAT tester has a high duty cycle, tailored towards fast, repetitive & continuous testing, and also offers the benefits of a 110V socket for industrial appliance testing and flash testing for servicing workshops. The Megger 450 tester is suited to almost any electrical safety testing application and as such is a versatile and long term investment for professional PAT test engineers and electrical contractors.
Key Features
- Extensive PAT testing functions including 110V operation and flash testing capabilities
- Large 10,000 record onboard memory with download functionality
- Large full colour display with test data and Pass/Fail indication
- Instant re-start retains data when temporarily disconnected
- Direct access keys and QWERTY keyboard for intuitive operation
- Productive appliance testing for service organisations and tool hire/repair companies
PAT320 | PAT350 | PAT410 | PAT420 | PAT450 | |
---|---|---|---|---|---|
Earth Bond Test | ✔ | ✔ | ✔ | ✔ | ✔ |
IT Safe (200mA test current) | ✔ | ✔ | ✔ | ✔ | ✔ |
Insulation Test (250V, 500V) | ✔ | ✔ | ✔ | ✔ | ✔ |
Substitute Leakage Test | ✔ | ✔ | ✔ | ✔ | ✔ |
Differential Leakage Test | ✔ | ✔ | ✔ | ✔ | ✔ |
Touch Current Test | ✔ | ✔ | ✔ | ✔ | ✔ |
Portable RCD Test | ✔ | ✔ | ✔ | ✔ | ✔ |
Extension Lead Test | ✔ | ✔ | ✔ | ✔ | ✔ |
Fuse Test | ✔ | ✔ | ✔ | ✔ | ✔ |
Operational Test | ✔ | ✔ | ✔ | ✔ | ✔ |
Flash Test | ✔ | ✔ | |||
230V and 110V Operation | ✔ | ✔ | ✔ | ✔ | |
Internal Memory (10,000 results) | ✔ | ✔ | ✔ | ||
Downloadable (USB) | ✔ | ✔ | ✔ | ||
QWERTY Keyboard | ✔ | ✔ | ✔ |
Earth Bond test (10A and 25A)
- Open circuit voltage: 9V AC (Supply 230V)
- Resistance accuracy: ±5% ±3 digits (0 to 0.49 Ω), ±5% ±5 digits 0.5 to .99 Ω)
- Resistance resolution: 10 mΩ (0 to 1.99 Ω)
- Display range: 0 to 1.99 Ω
Continuity test (200mA)
- Voltage: 4V DC
- Resistance accuracy: ±5% ±3 digits (0 to 0.49 Ω), ±5% ±5 digits 0.5 to .99 Ω)
- Resistance resolution: 10 mΩ (1 to 19.99 Ω)
- Display range: 0 to 19.99 Ω
Insulation test (250/500V)
- Resistance accuracy: ±2% ±5 digits (0 to 19.99 MΩ), ±5% ±10 digits (20 to 99.99 MΩ)
- Resistance resolution: 0.01 MΩ
- Display range: 0 to 99.99 MΩ
Substitute leakage test
- Voltage: 40V AC nominal mains frequency
- Current accuracy: ±5% ±5 digits
- Current resolution: 0.01mA
- Display range: 0 to 19.99mA
Differential leakage test
- Voltage: Nominal mains supply
- Current accuracy: ±5% ±5 digits
- Current resolution: 0.01mA
- Display range: 0 to 19.99mA
Touch current test
- Voltage: Nominal mains supply
- Current accuracy: ±5% ±5 digits
- Current resolution: 0.01mA
- Display range: 0 to 10mA
Operational test
- Voltage: Nominal mains supply
- VA accuracy: ±5% ±10 digits (0 - 99 VA), ±5% ±50 digits (100 VA - 999 VA), ±5% ±100 digits (1000 VA - 3700 VA)
- Resolution: 1 VA (0 to 3700 VA)
- Display range: 0 to 3999 VA
Extension lead test
- Tests performed: Bond, insulation and polarity
- Polarity test voltage: 12V
- Polarity checks: Lead OK, Live neutral S/C, Live neutral reversed, Live/neutral O/C
Portable RCD test
- Voltage: Nominal mains supply
- Current accuracy: -8% to -2% (1/2 x I), +2% to +8% (1 x I, 5 x I)
- Trip time accuracy: ±1% ±5 digits
- Trip time resolution: 0.1ms
- Display range: 0 to 1999 ms (1/2 x I), 0 to 300 ms (1 x I), 0 to 40 ms (5 x I)
Fuse test
- Voltage: 3.3V
- Warning: Audible bleep if fuse is OK
Flash test
- Voltage: 1500V AC for Class 1, 3000V AC for Class2
- Current: <3.5 mA short circuit @ 253 V
- Breakdown current accuracy: ±5% ±5 digits
- Breakdown current resolution: 0.01mA
- Display range: 0 to 3mA
- Supply range: 230V at 50Hz, 110V at 50Hz
- Compliance: IEC 61010-1, CAT II 300V, IEC 61326-1, 61326-2-2
- Dimensions: 180 x 255 x 320mm
- Weight: 5kg
The Megger PAT450 comes with:
- Earth Bond Test Lead
- Extension Lead Adaptor
- Cloverleaf Adaptor
- Flash Test Lead
- Calibration Certificate
- Instruction Manual & CD
- Carry Case
The Megger PAT450 PAT Tester is available in a range of kits:
Kit A | Kit B | Kit C | Kit D | Kit E | |
---|---|---|---|---|---|
Megger PAT450 Tester | ✔ | ✔ | ✔ | ✔ | ✔ |
Megger Powersuite Pro Lite PAT Software | ✔ | ✔ | |||
Megger Powersuite Professional Contractor PAT Software | ✔ | ✔ | |||
Megger PAT Label Printer | ✔ | ✔ | ✔ | ||
Megger PAT Label Cartridges | 2 | 2 | 2 | ||
Megger Barcode Scanner | ✔ | ✔ | ✔ | ||
Microwave Leakage Detector | ✔ | ✔ | ✔ | ✔ | |
150 Microwave Emissions Labels | ✔ | ✔ | ✔ | ✔ | |
IEC Clover Leaf Adaptor | ✔ | ✔ | ✔ | ✔ | ✔ |
IEC PAT Adaptor Kit | ✔ | ✔ | ✔ | ✔ | ✔ |
110V Extension Lead Adaptor | ✔ | ✔ | ✔ | ✔ | ✔ |
Pass Labels | 1000 | 500 | 1000 | 1000 | 1000 |
Fail Labels | 400 | 200 | 400 | 400 | 400 |
250 PassWrap Cable Labels | ✔ | ✔ | ✔ | ✔ | |
Earth Bond Test Lead | ✔ | ✔ | ✔ | ✔ | ✔ |
230V Extension Lead Adaptor | ✔ | ✔ | ✔ | ✔ | ✔ |
Calibration Certificate | ✔ | ✔ | ✔ | ✔ | ✔ |
PAT450 Carry Case | ✔ | ✔ | ✔ | ✔ | ✔ |
Available For Hire: £105 Per Week (exc. VAT)
Optional Extras:
- Download service (£39+VAT) - Our download service saves you time by providing all your PAT testing results in a digital format of your choice. Simply return the hire tester and we'll email you the results asap.
Free Gifts - Receive 200 Pass and 200 Fail labels free when you hire a tester from PAT-Testers.co.uk.
Shipping - We are happy to arrange delivery & collection of hire equipment at a cost of £10 each way (optional).
Booking a PAT Tester with us is simple:
- Choose a tester from our hire fleet
- Decide the dates you need the tester
- Call us on 0113 248 9966 to book or click the button below