Metrel A1322 Active 3-Phase Adaptor
- Active polarity test, differential leakage test, 3-phase RCD test
- Suitable for testing industrial extension leads with RCD trips
- Ideal for troubleshooting andperiodic testing on three-phase equipment
Metrel’s all new A 1322 Multifunctional 3 Phase test adapter is designed for troubleshooting, as well as for periodic testing on 3-phase appliances and machinery. Unique functions such as, active polarity testing, differential leakage testing and testing of 3-phase RCD’s make the A1322 Active 3-phase Adapter an ideal instrument for advanced applications. The Metrel A1322 adapter is designed for use alongside the MI3321 MultiservicerXA, SigmaPAT & DeltaPAT enabling functional tests to be carried out on machines up to 40A. Several test socket outlets make this instrument an ideal tester for testing industrial extension leads that may also be RCD protected. Due to the powerful test data management included with both supporting test instruments, all test data can easily be equipped with needed parameters. This data can be stored into the large memory included, and with the support of the powerful data management system PC SW Patlink Pro, exported as professional test reports.
Key Features
- All tests on 3-phase electrical equipment
- 3 Phase Live leakage test
- 3 Phase differential Leakage Testing
- Insulation Resistance
- 3 Phase Power testing (kVA, kW, kVAr & Cos)
- RCD (3-Phase P/RCD Testing) Type (AC,A,B, PRCD-S & P/RCD-K)
- Simple connection to the PAT/MACHINE tester with automatic detection.
- Simple test procedures, identical to single phase equipment.
- Test sequence for 3-phase tests are automatically set, based on entered test codes and input voltages.
- Built-in CEE 3-PH/32A 5 pin, CEE 3-PH/16A 5 pin and CEE 1-PH/16A 3 pin test sockets.
- Robust waterproof case
Differential leakage current (230/400 VAC or 120/208 VAC)
- Differential leakage current accuracy: 0.00 mA ÷ 9.99 mA 0.01 mA ±(5 % of reading + 5 digits)
- Power / Functional test (230/400 VAC or 120/208 VAC)
- Apparent power accuracy: 0.00 kVA ÷ 24.29 kVA 0.01 kVA ±(5 % of reading + 5 digits)
- Active power readout Range Resolution Accuracy 0.00 kW ÷ 24.29 kW 0.01 kW ±(5 % of reading + 5 digits)
- Reactive power readout Accuracy 0.00 kW ÷ 24.29 kVAr 0.01 kVAr ±(5 % of reading + 5 digits)
- Power factor readout Range Resolution Accuracy 0.00 ÷ 1.00 0.01 ±(5 % of reading + 5 digits)
- 3-phase RCD / Test current (10 mA, 15 mA, 30 mA, 100 mA, 300 mA)
- Portable RCD trip-out time readout (AC and A type PRCD)
- Range Resolution Accuracy
- 0 ms ÷ 300 ms (½ x IΔN, IΔN ) 1 ms
- 0 ms ÷ 150 ms (2 x IΔN) 1 ms ±3 ms
- 0 ms ÷ 40 ms (5 x IΔN) 1 ms
- Portable RCD trip-out current readout (B type PRCD)
- Range Resolution Accuracy
- 0.2 x IΔN ÷ 2.2 x IΔN 0.05 x IΔN ±0.1 x IΔN
- Polarity test Standard test (<60 VAC and DC)
- Polarity test Active (Mains supply voltage, over-current protection)
General data
- Supply voltage single-phase 230 V ±10 %
- Supply voltage 3-phase 230/400 V ±10 %
- 120/208 V ±10 %
- Maximum test current 32 A, 40 A max (10 min)
- Overvoltage category 300 V/CAT II
- Protection classification I
- Pollution degree 2
- Protection degree IP 65 (closed and locked cover) / IP 20 (connectors)
- Case Shock proof plastic, portable
- Dimensions: 335 mm x 160 mm x 335 mm
- Weight (without accessories) 7.2 kg