Kewtech EZYPAT Kit C
- Ideal for routine in-house PAT testing of power tools and office equipment
- Adaptors included for 110V appliances and power tools and IEC leads
- Microwave leakage detector and socket tester provide additional capabilities
Kewtech EZYPAT Kit C is a comprehensive solution to low-volume PAT testing on construction sites and in offices. The main instrument in the kit is the Kewtech EZYPAT PAT Tester. This tester can perform earth bond, insulation, substitute leakage and polarity checks in automatic test sequences for Class I appliances, Class II appliances and IEC/extension leads. Clearly-labelled push buttons make the tester very easy to use and results are clearly shown on the bright digital screen.
There is a full range of adaptors in Kewtech EZYPAT Kit C for 110V appliances and extension leads as well as IEC leads and power cords often used in IT and audiovisual equipment. Additionally, there is a socket tester and a microwave leakage detector whilst a PAT certificate pad and register book make it easy to record test results. There are PAT labels for both indoor and outdoor use and there is a Kewtech carry case for all the components.
For more information on the Kewtech EZYPAT PAT Tester, please click here.
Kit Contents
- Kewtech EZYPAT PAT Tester
- Two rolls of PASS label rolls (x500)
- FAIL label roll (x200)
- PassWrap labels (x250)
- Tuff Tag labels (x250)
- Microwave labels (x50)
- 2 x PAT register books
- IEC adaptor kit
- Kewtech KT103 socket tester
- 110V appliance adaptor
- 110V extension lead adaptor
- IEC adaptor kit
- Microwave leakage detector
- PAT certificate pad
- PAT register book
Kit A | Kit B | Kit C | |
---|---|---|---|
Kewtech EZYPAT PAT Tester | ✔ | ✔ | ✔ |
PASS labels | x2 | x2 | x2 |
FAIL labels | ✔ | ✔ | ✔ |
PassWrap labels | ✔ | ✔ | ✔ |
Tuff Tag Pass Labels | ✔ | ✔ | |
PAT certificate pad | ✔ | ✔ | ✔ |
PAT registerbook | x1 | x1 | x2 |
IEC clover leaf adaptor | ✔ | ||
IEC adaptor kit | ✔ | ✔ | |
110V appliance adaptor | ✔ | ✔ | |
110V extension lead adaptor | ✔ | ✔ | |
Kewtech KT103 Socket Tester | ✔ | ✔ | ✔ |
Microwave leakage detector | ✔ | ✔ | |
Microwave emission labels | ✔ | ✔ | |
Kewtech KITBAG2 carry case | ✔ | ✔ |
Protective Conductor Resistance
- Measuring range: 0.00 - 20.00 Ω (NULL value inc)*
- Over-range indication: > 20.00 Ω
- Resolution: 0.01Ω
- Open-circuit voltage: 5 V ±0.4 V DC
- Measuring current: 200 mA DC (nominal value)
- Accuracy: ±3%rdg ±5dgt
Insulation
- Rated voltage: 250V / 500V
- Measuring range: 0.00 - 20.00 MΩ
- Over-range indication: > 20.00 MΩ
- Resolution: 0.01 MΩ
- No-load voltage: 250 V DC +20%, -0% / 500 V DC +20%, -0%
- Short-circuit current: 1.5 mA DC or less
- Rated current: 1 -1.2 mA with a load of 0.25 MΩ / 1 to 1.2 mA with a load of 0.5 MΩ
- Accuracy: ±2%rdg±3dgt
Substitute Leakage
- Measuring range: 0.10 - 12.00 mA rms
- Over-range indication: > 12.00 mA
- Resolution: 0.01mA
- Open-circuit voltage/ Freq.: 30 V ±5 V rms / 50 Hz ±5%
- Measuring current: 1.2 mA AC ±0.5 mA (when measuring 12.00 mA)
- Accuracy: ±3%rdg±5dgt
Applicable Standards
- Safety: IEC/EN61010-1 CAT II 300V-instrument; IEC/EN61010-2-030; IEC/EN61010-031 CAT III 600V
- EMC: EN61326-1, 2-2
- Possible number of measurements where battery voltage is within the effective range (measuring every 30 sec): Approx. 1400 times (CLI Rpe: 0 Ω, Rins: 1.1 MΩ)
- Kewtech EZYPAT PAT Tester
- Two rolls of PASS label rolls (x500)
- FAIL label roll (x200)
- PassWrap labels (x250)
- Tuff Tag labels (x250)
- Microwave labels (x50)
- 2 x PAT register books
- IEC adaptor kit
- Kewtech KT103 socket tester
- 110V appliance adaptor
- 110V extension lead adaptor
- IEC adaptor kit
- Microwave leakage detector
- PAT certificate pad
- PAT register book